VFD Aux Pump does not start. #4
Labels
VFD
issues relating to the Variable Frequency Drive
water cooling
issues related to the water cooling system for the spindle
The VFD's relay output does not operate when configured as the aux pump output.
With the following parameters set (where non-default),
PD130: 1 - no. of aux pumps
PD052: 25 - output F: aux pump 1
relay is expected to operate on run-start and release 20s after run-stop.
Relay output confirmed working by setting:
PD052: 01 - output F: in run
This setting stops the pumps as soon as the motor has stopped, which in practice is probably sufficient.