i have an ms200 module with a cs200 control unit from bosch. 2 collector arrays are connected to it and the system is used as heating support. the valve status is also displayed, but it does not change even if the valve is open
I use this configuration (GHK):
in Ems-ESP i have the heat assist valve m1 should this be vs1 or vs 3 ?
and the temprature ts8 is not displayed in ems-esp.
The valves we expect here: solar(0x30) -B-> All(0x00), SM100Status2(0x036A), data: 03 03 03 03 03 03 03 03 03 03 04 03
Offset 10 with value 04 means pump switched on, all valves closed. Can you switch the valve manally or trigger a switching? Then log a minute before and a minute after switching the valve to see the change.
We have VS1 in offset 0, VS2 in offset 4, M1 in offset 7, Pump1 in offset 10 and pump2 in offset1, all other values are unknown.
Do you have a name for TS8? Looks lke offset 22 in 0x362 solar(0x30) -B-> All(0x00), SM100Monitor(0x0362), data: 02 36 00 CE 80 00 00 C1 01 2C 01 80 80 00 80 00 80 00 80 00 80 00 01 A8
with value 42.4°C (0x01A8).
i have an ms200 module with a cs200 control unit from bosch. 2 collector arrays are connected to it and the system is used as heating support. the valve status is also displayed, but it does not change even if the valve is open
I use this configuration (GHK):
in Ems-ESP i have the heat assist valve m1 should this be vs1 or vs 3 ?
and the temprature ts8 is not displayed in ems-esp.
Here ist my log: