Notifications
You must be signed in to change notification settings - Fork 1
/
Copy pathpsych.h
446 lines (389 loc) · 11.6 KB
/
psych.h
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
/*
* psych.h
*
* Created on: Dec 26, 2016
* Author: Todd Miller
*
*/
#ifndef PSYCH_H
#define PSYCH_H
#include <math.h>
double part_press( double P, double W )
/*
* Function to compute partial vapor pressure in [kPa]
* From page 6.9 equation 38 in ASHRAE Fundamentals handbook (2005)
* P = ambient pressure [kPa]
* W = humidity ratio [kg/kg dry air]
*/
{
return P * W / (0.62198 + W);
}
double sat_press( double Tdb)
/*
* Function to compute saturation vapor pressure in [kPa]
* ASHRAE Fundamentals handbook (2005) p 6.2, equation 5 and 6
* Tdb = Dry bulb temperature [degC]
* Valid from -100C to 200 C
*/
{
double
TK = 173.15,
C1 = -5674.5359,
C2 = 6.3925247,
C3 = -0.009677843,
C4 = 0.00000062215701,
C5 = 2.0747825E-09,
C6 = -9.484024E-13,
C7 = 4.1635019,
C8 = -5800.2206,
C9 = 1.3914993,
C10 = -0.048640239,
C11 = 0.000041764768,
C12 = -0.000000014452093,
C13 = 6.5459673;
TK = Tdb + 273.15; //Converts from degC to degK
if(TK <= 273.15)
{
return exp(C1 / TK + C2 + C3 * TK + C4 * pow(TK, 2) + C5 * pow(TK, 3) + C6 * pow(TK, 4) + C7 * log(TK)) / 1000;
}
else
{
return exp(C8 / TK + C9 + C10 * TK + C11 * pow(TK, 2) + C12 * pow(TK, 3) + C13 * log(TK)) / 1000;
}
}
double hum_rat(double Tdb, double Twb, double P)
/*
* Function to calculate humidity ratio [kg H2O/kg air]
* Given dry bulb and wet bulb temperature inputs [degC]
* ASHRAE Fundamentals handbook (2005)
* Tdb = Dry bulb temperature [degC]
* Twb = Wet bulb temperature [degC]
* P = Ambient Pressure [kPa]
*/
{
double Pws = sat_press(Twb);
double Ws = 0.62198 * Pws / (P - Pws); // Equation 23, p6.8
if(Tdb >= 0)
{
// Equation 35, p6.9
return ((2501 - 2.326 * Twb) * Ws - 1.006 * (Tdb - Twb)) / (2501 + 1.86 * Tdb - 4.186 * Twb);
}
else
{
// Equation 37, p6.9
return ((2830 - 0.24 * Twb) * Ws - 1.006 * (Tdb - Twb)) / (2830 + 1.86 * Tdb - 2.1 * Twb);
}
}
double hum_rat2(double Tdb, double RH, double P)
/*
* Function to calculate humidity ratio [kg H2O/kg air]
* Given dry bulb and wet bulb temperature inputs [degC]
* ASHRAE Fundamentals handbook (2005)
* Tdb = Dry bulb temperature [degC]
* RH = Relative Humidity [Fraction or %/100]
* P = Ambient Pressure [kPa]
*/
{
double Pws = sat_press(Tdb);
return 0.62198 * RH * Pws / (P - RH * Pws); // Equation 22, 24, p6.8
}
double rel_hum(double Tdb, double Twb, double P)
/*
* Calculates relative humidity ratio
* ASHRAE Fundamentals handbood (2005)
* Tdb = Dry bulb temperature [degC]
* Twb = Wet bulb temperature [degC]
* P = Ambient Pressure [kPa]
*/
{
double W = hum_rat(Tdb, Twb, P);
return part_press(P, W) / sat_press(Tdb); // Equation 24, p6.8
}
double rel_hum2(double Tdb, double W, double P)
/*
* Calculates the relative humidity
* Tdb = Dry bulb temperature [degC]
* W = humidity ratio [kg/kg dry air]
* P = ambient pressure [kPa]
*/
{
return part_press(P, W) / sat_press(Tdb);
}
double wet_bulb(double Tdb, double RH, double P)
/*
* Calculates the Wet Bulb temperature [degC]
* Uses Newton-Rhapson iteration to converge quickly
* Tdb = Dry bulb temperature [degC]
* RH = Relative humidity ratio [Fraction or %]
* P = Ambient Pressure [kPa]
*/
{
double W_normal = hum_rat2(Tdb, RH, P);
// Solve to within 0.001% accuracy using Newton-Rhapson
double Wet_bulb = Tdb; // initialize at saturation
double W_new = hum_rat(Tdb, Wet_bulb, P);
do
{
double W_new2 = hum_rat(Tdb, Wet_bulb - 0.001, P);
double dw_dtwb = (W_new - W_new2) / 0.001;
double Wet_bulb = Wet_bulb - (W_new - W_normal) / dw_dtwb;
W_new = hum_rat(Tdb, Wet_bulb, P);
}
while (abs((W_new - W_normal) / W_normal) > 0.00001);
return Wet_bulb;
}
double enthalpy_air_h2o(double Tdb, double W)
/*
* Calculates enthalpy in [kJ/kg dry air]
* From 2005 ASHRAE Handbook - Fundamentals - SI P6.9 eqn 32
* Tdb = Dry bulb temperature [degC]
* W = Humidity Ratio [kg/kg dry air]
*/
{
return 1.006 * Tdb + W * (2501 + 1.86 * Tdb);
}
double dew_point(double P, double W)
/*
* Calculates dew point temperature [deg C]
* From page 6.9 equation 39 and 40 in ASHRAE Fundamentals handbook (2005)
* P = ambient pressure [kPa]
* W = humidity ratio [kg/kg dry air]
* Valid for Dew Points less than 93 C
*/
{
double
C14 = 6.54,
C15 = 14.526,
C16 = 0.7389,
C17 = 0.09486,
C18 = 0.4569;
double Pw = part_press(P, W);
double alpha = log(Pw);
double Tdp1 = C14 + C15 * alpha + C16 * pow(alpha, 2) + C17 * pow(alpha, 3) + C18 * pow(Pw, 0.1984);
double Tdp2 = 6.09 + 12.608 * alpha + 0.4959 * pow(alpha, 2);
if (Tdp1 >= 0)
{
return Tdp1;
}
else
{
return Tdp2;
}
}
double dry_air_density(double P, double Tdb, double W)
/*
* Calculates dry air density [kg_dry_air/m^3]
* From page 6.8 equation 28 ASHRAE Fundamentals handbook (2005)
* P = pressure [kPa]
* Tdb = Dry bulb temperature [degC]
* W = humidity ratio [kg/kg dry air]
*
* Note that total density of air-h2o mixture is:
* rho_air_h2o = rho_dry_air * (1 + W)
*/
{
double R_da = 287.055; // gas constant for dry air
return 1000 * P / (R_da * (273.15 + Tdb) * (1 + 1.6078 * W));
}
/*
* Use these functions below to calculate atmospheric pressure
* Try the MPL3115A2, BMP180, or T5403 pressure sensor from Sparkfun.com
* to compute real-time pressure readings, or better if measured in an air
* duct use two pressure sensors with a Dwyer Instruments 160E pitot tube.
* Readings from the pitot tube will give static pressure and tip pressure.
* See https://www.grc.nasa.gov/WWW/K-12/airplane/pitot.html to solve for
* air speed.
*/
double STD_press(double elevation)
/*
* Calculates the standard pressure [kPa]
* elevation = height relative to sea level [m]
* ASHRAE Fundamentals 2005 - chap 6, eqn 3
* Valid from -5000m to 11000m
*/
{
return 101.325 * pow(1 - 0.0000225577 * elevation, 5.2559);
}
double STD_temp(double elevation)
/*
* Calculates the standard temperature [degC] at given elevation [m]
* ASHRAE Fundamentals 2005 - chap 6, eqn 4
* Valid from -5000m to 11000m
*/
{
return 15 - 0.0065 * elevation;
}
double psych(double P, double Tdb, int inValue, int inType, int outType, int SIq)
{
/*
* P is the barometric pressure in PSI or Pa.
* Tdb is the dry bulb in F or C
* inValue is another parameter of choice (Wet bulb, Dew point, RH, Humidity Ratio, or Enthalpy)
* inType is the number that corresponds to your choice of InV's parameter (1 through 4 or 7 respectively)
* outType is the value requested. It should be an integer between 1 and 10 excluding 8. See below
* SIq is the unit selector. 0 is IP, 1 is SI
* The choices for inType and outType are:
* 1 Web Bulb Temp F or C Valid for Input
* 2 Dew point F or C Valid for input
* 3 RH between 0 and 1 Valid for input
* 4 Humidity Ratio Mass Water/ Mass Dry Air Valid for input
* 5 Water Vapor Pressure PSI or Pa
* 6 Degree of Saturation between 0 and 1
* 7 Enthalpy BTU/lb dry air or kJ/kg dry air Valid for input
* Warning 0 state for IP is ~0F, 0% RH ,and 1 ATM, 0 state for SI is 0C, 0%RH and 1 ATM
* 8 NOT VALID, Should be entropy
* 9 Specific Volume ft^3/lbm or m^3/kg dry air
* 10 Moist Air Density lb/ft^3 or m^3/kg
*/
double Twb, Dew, RH, W, h, out;
if(SIq == 1)
{
P = P / 1000; // Turns Pa to kPA
switch(inType)
{
case 1:
Twb = inValue;
break;
case 2:
Dew = inValue;
break;
case 3:
RH = inValue;
break;
case 4:
W = inValue;
break;
case 7:
h = inValue;
break;
}
}
else // This section turns US Customary Units to SI units
{
Tdb = (Tdb - 32) / 1.8;
P = P * 4.4482216152605 / pow(0.0254, 2) / 1000; // PSI to kPa Conversion factor exact
switch(inType)
{
case 1:
Twb = (inValue- 32) / 1.8; // F to C
break;
case 2:
Dew = (inValue- 32) / 1.8; // F to C
break;
case 3:
RH = inValue; // no need to change
break;
case 4:
W = inValue; // no need to change
break;
case 7:
h = inValue * 1.055056 / 0.45359237 - 17.884444444;
// 1.055056 kJ/(ISO_BTU) .45359237 kg/lb
// 17.884444 kJ/kg 0 pt difference [Dry air at 0C and dry air at 0F are both 0 enthalpy in their respective units]
break;
}
}
if(outType == 3 || outType == 1) // Find RH
switch(inType)
{
case 1: // given Twb
RH = rel_hum(Tdb, Twb, P);
break;
case 2: // given Dew
RH = sat_press(Dew) / sat_press(Tdb);
break;
case 3: // given RH
break;
// RH already Set
case 4: // given W
RH = part_press(P, W) / sat_press(Tdb);
break;
case 7:
W = (1.006 * Tdb - h) / (-(2501 + 1.86 * Tdb));
// Algebra from 2005 ASHRAE Handbook - Fundamentals - SI P6.9 eqn 32
RH = part_press(P, W) / sat_press(Tdb);
break;
}
else // find W
switch(inType)
{
case 1: // Given Twb
W = hum_rat(Tdb, Twb, P);
break;
case 2: // Given Dew
W = 0.621945 * sat_press(Dew) / (P - sat_press(Dew));
break;
// Equation taken from eq 20 of 2009 Fundamentals chapter 1
case 3: // Given RH
W = hum_rat2(Tdb, RH, P);
break;
case 4: // Given W
// W already known
case 7: // Given h
W = (1.006 * Tdb - h) / (-(2501 + 1.86 * Tdb));
// Algebra from 2005 ASHRAE Handbook - Fundamentals - SI P6.9 eqn 32
break;
}
// P, Tdb, and W are now available
switch(outType)
{
case 1: // requesting Twb
out = wet_bulb(Tdb, RH, P);
break;
case 2: // requesting Dew
out = dew_point(P, W);
break;
case 3: // Request RH
out = RH;
break;
case 4: // Request W
out = W;
break;
case 5: // Request Pw
out = part_press(P, W) * 1000;
break;
case 6: // Request deg of sat
out = W / hum_rat2(Tdb, 1, P);
// the middle arg of Hum_rat2 is suppose to be RH. RH is suppose to be 100%
break;
case 7: // Request enthalpy
out = enthalpy_air_h2o(Tdb, W);
break;
case 8: // Request entropy
out = -9999;
// don't have equation for Entropy
break;
case 9: // Request specific volume
out = 1 / (dry_air_density(P, Tdb, W));
break;
case 10: // Request density
out = dry_air_density(P, Tdb, W) * (1 + W);
break;
}
if(SIq == 0) // Convert to IP
switch(outType)
{
case 1: // Temperature
out = (1.8 * out) + 32;
break;
case 2: // Temperature
out = (1.8 * out) + 32;
break;
// OutNum 3 and 4 (RH and W) are unitless
case 5: // Pressure
out = out * pow(0.0254, 2) / 4.448230531;
break;
case 7: // Enthalpy
out = (out + 17.88444444444) * 0.45359237 / 1.055056;
// Warning, 0 convention changes. Be careful with units.
break;
case 9: // Specific Volume
out = out * 0.45359265 / (pow(12 * 0.0254, 3));
break;
case 10: // Density
out = out * pow(12 * 0.0254, 3) / 0.45359265;
break;
}
return out;
}
#endif